Efficient motor, adjustable speed
An electronically commutated motor drives the backward-curved centrifugal impeller. Rated for continuous operation, with automatic restart after thermal protection trips.
Recent
Vider
Commercial & Residential | Supply & Extract | 1-phase EC
One EC fan for 150 mm or 160 mm ducts.
CENTRO EC 150 is an inline centrifugal fan with connections for both 150 mm and 160 mm circular ductwork. Its high-efficiency, 82 W EC motor provides maximum airflow of 630 m³/h (175 l/s) for commercial and residential supply or extract ventilation.
The external 0–10 V input accepts a signal from an EC speed controller, sensor controller or compatible BMS. Mounting brackets are included. The same CENTRO-EC-150 model serves either duct size; external controls and ductwork are supplied separately.

An electronically commutated motor drives the backward-curved centrifugal impeller. Rated for continuous operation, with automatic restart after thermal protection trips.
Accepts a speed signal from an external EC controller, sensor controller or building management system. Controls are supplied separately.
The moulded ABS housing has circular duct connections and an external terminal box. Unit protection is IPX4; motor protection is IP44.
Two mounting brackets support floor, wall or ceiling fixing. The fan can be installed horizontally or vertically, following the user guide.

CENTRO EC 150 covers both connection sizes without moving to a different fan model. Both sizes use the same 82 W motor and published CENTRO EC 150 data, with maximum airflow of 630 m³/h. The backward-curved centrifugal impeller is designed for ducted supply or extract ventilation.
View CENTRO EC 150 technical dataThe fan has a 286 mm overall length and weighs 2.5 kg. Two supplied brackets allow it to be fixed to a floor, wall or ceiling along the duct route. The external terminal box is accessible for wiring, and the removable cover provides access for cleaning. Model dimensions are shown below.
View CENTRO EC 150 technical data

Order CENTRO-EC-150 for the standard 150 / 160 mm EC fan. The box contains the fan, two mounting brackets, fixing screws and dowels, and the user guide. One product reference covers both duct sizes. The external controller, any sensors and the ductwork are supplied separately.
View CENTRO EC 150 technical data
The fan can stay in its service space while an external EC controller adjusts its speed. A compatible CO₂ or humidity controller can also change that speed automatically through the 0–10 V input. The fan has no built-in room sensor, so the controls can be selected for the way the space is used.
Talk to us about your projectA separate EC speed controller sets the fan speed through its 0–10 V input. For automatic adjustment, a compatible sensor controller or building management system (BMS) can supply that signal instead. For example, an external CO₂ or humidity controller can vary speed as conditions change. The standard fan has no built-in room sensor or user speed control.
The EC motor has thermal protection with automatic restart. Isolate the electrical supply before opening or cleaning the fan. Inspect and clean it at least every six months, following the user guide.

| Specification | CENTRO EC 150 |
|---|---|
| Model | CENTRO-EC-150 |
| Duct connection | 150 / 160 mm |
| Maximum airflow | 630 m³/h (175 l/s) |
| Motor | Electronically commutated (EC) |
| Speed control signal | 0–10 V |
| Electrical supply | 1-phase |
| Frequency | 50/60 Hz |
| Rated power | 82 W |
| Current | 0.63 A |
| Speed | 3400 rpm |
| Sound pressure at 3 m | 45 dBA |
| Transported air temperature | −25 to +60 °C |
| Ambient operating temperature | +1 to +40 °C |
| Unit ingress protection | IPX4 |
| Motor ingress protection | IP44 |
| Thermal protection | Automatic restart |
| Weight | 2.5 kg |
Maximum airflow is the catalogue maximum, not the airflow at every installed duty. Select from the fan curve at the required airflow and system resistance. Sound figures are sound pressure levels at 3 m; room noise depends on the duty and installation.

| Specification | CENTRO EC 150 |
|---|---|
| D - duct connection | 150 / 160 mm |
| D1 | 300 mm |
| B | 310 mm |
| L - overall length | 286 mm |
| L1 | 30 mm |
| L2 | 30 mm |
| L3 | 30 mm |
D, D1, B, L, L1, L2 and L3 correspond to the manufacturer drawing. Dimensions are in mm. Weight is in kg. Allow additional room for connections and maintenance.
For help choosing the fan or a compatible controller, send Blauberg UK the duct size, required airflow and system pressure. CENTRO EC is for general clean-air ventilation; specialist process extract, commercial kitchen grease extract and smoke control require a different fan selection.
Yes, building regulations for extractor fans fall under Part F of the Building Regulations, which deals with ventilation requirements, and Part L, which focuses on the conservation of fuel and power. For new builds and major renovations, installing an extractor fan to ensure adequate ventilation is mandatory. This applies to rooms such as bathrooms, kitchens, and utility rooms to prevent issues like mould and indoor air pollution. The specific airflow rates that need to be met vary based on the room and usage.
The Blauberg CENTRO-EC-150 meets both Part F and Part L regulations, ensuring it provides adequate ventilation while being energy-efficient. This compliance means it helps maintain good indoor air quality and conserves energy, which is essential for both environmental sustainability and reducing energy costs. Meeting these regulations ensures the ventilation system is up to modern standards and contributes to a healthier living environment.
EC (Electronically Commutated) fans are controlled using advanced electronics that adjust the fan's speed based on the ventilation demand. This precise control allows for efficient energy use and optimised airflow. Unlike traditional AC motors, EC motors can operate at various speeds without the need for additional components, providing more flexibility and efficiency.
The ability to control the fan speed dynamically means that EC fans can adapt to the specific ventilation needs of different environments, whether it’s a residential, commercial, or industrial setting. This adaptability not only improves energy efficiency but also extends the lifespan of the fan by reducing wear and tear associated with running at constant speeds.
Specific Fan Power (SFP) regulations refer to the energy efficiency of ventilation systems, measured in watts per liter per second of airflow. The lower the SFP, the more efficient the fan. For compliance, fans must meet the maximum SFP values specified in building regulations to ensure energy-efficient operation and reduced environmental impact.
Adhering to SFP regulations is crucial for ensuring that ventilation systems are not only effective but also economical to run. It ensures that the fans contribute to overall energy savings, which is beneficial both for reducing operational costs and for meeting environmental sustainability goals.
To calculate the Specific Fan Power (SFP) of a fan, you divide the total power input (in watts) by the airflow rate (in litres per second). The formula is:
SFP = Total Power Input (W) / Airflow Rate (l/s)
Understanding and calculating SFP is essential for selecting the right fan for your needs. It helps in comparing the efficiency of different fans and choosing one that will provide the necessary airflow with minimal energy consumption, thereby optimising both performance and cost.
Complying with Part L of the Building Regulations is crucial because it focuses on the conservation of fuel and power. Ensuring that building components, including ventilation systems, are energy efficient helps reduce overall energy consumption, lower greenhouse gas emissions, and meet sustainability goals.
This compliance also contributes to reducing operational costs and improving the environmental footprint of buildings. By using energy-efficient systems, buildings can achieve better ratings and meet modern standards that are increasingly important for both regulatory purposes and for the well-being of occupants.
EC fans are considered the most energy-efficient fans due to their advanced motor technology, which allows for precise speed control and lower power consumption. Their design enables better conversion of electrical energy into mechanical energy, reducing energy waste.
The efficiency of EC fans not only makes them cost-effective to operate but also aligns with modern environmental standards. Their ability to adapt to varying ventilation needs ensures that they operate only as much as necessary, thus avoiding unnecessary energy use and contributing to overall energy conservation efforts.
Several factors contribute to a fan's energy efficiency: - **Advanced Motor Technology:** EC motors are more efficient than traditional AC motors. - **Speed Control:** Ability to adjust speed based on demand reduces unnecessary energy use. - **Design:** Features like backward-curved blades improve airflow efficiency. - **Low Heat Generation:** Less heat production during operation extends the motor's lifespan and reduces cooling requirements.
These factors combined make EC fans a superior choice for anyone looking to improve their ventilation system's efficiency. The precise control and advanced design features ensure that these fans provide optimal performance while minimising energy consumption and operational costs.
The Blauberg CENTRO-EC-150 is a powerful inline bathroom extractor fan, offering a maximum airflow rate of 630 m³/hour (175 l/s) with a noise level of only 45 dB(A). This fan is suitable for high-pressure duct installations and provides efficient, quiet operation.
This fan's high performance and quiet operation make it ideal for use in residential and commercial settings where noise levels are a concern. Its powerful airflow ensures effective ventilation, maintaining good air quality and comfort in bathrooms and other spaces.
Extractor fans, especially those with EC motors, do not use a lot of electricity. For instance, the Blauberg CENTRO-EC-150 consumes only 82 watts at maximum power, ensuring minimal impact on energy bills while maintaining high performance.
The energy-efficient design of EC fans means that they provide the necessary ventilation without significantly increasing energy consumption. This makes them a cost-effective solution for maintaining good indoor air quality without incurring high operational costs.
The cost to run a fan per hour depends on its power consumption and the cost of electricity. For example, with the Blauberg CENTRO-EC-150 consuming 82 watts, and assuming an electricity cost of £0.15 per kWh, the cost would be approximately £0.0123 per hour (82 watts / 1000 x £0.15).
Understanding the running costs helps in budgeting for the long-term use of the fan and evaluating its cost-effectiveness. With low operational costs, EC fans are an economical choice for ensuring efficient and effective ventilation.
| EAN Number | 5060407918556 |
|---|---|
| Impeller Type | Centrifugal |
| Motor Type | EC |
| Electrical Supply | 1 Phase 220/250 50/60Hz |
| Size | 150mm |
| Maximum Airflow Rate (l/s) | 417 |
| Maximum Airflow Rate (m3/h) | 1500 |
| Control Options | Standard |
| Duct Connection Size | 150mm Dia |
| Motor Temperature Class | Class B |
| Power (Watts) | 82w |